EI Programming Manual

Water Specialist EI
Control Valve
Programming and Cover Drawing Manual

ei_programming.JPG

The following instruction must be followed when programming the WS1EI – WS2EI as an
alternator.
Valve A:
1. In Confi guration Settings Step 3CS, VOLUME (M3) must be selected.
2. In Confi guration Settings Step 4CS, “On 0” must be selected.
3. In Confi guration Settings Step 5CS, Alt A must be selected. The “A” control is the one
connected to the “A” port of the MAV Motorized Alternating Valve and has the two pin wire
connector from the MAV Motorized Alternating Valve connected to it.
4. In Volume Installer Display Settings Step 2I, enter the volumetric capacity for the system.
5. In Volume Installer Display Settings Step 3I, set Days Override to OFF.


Valve B:
1. In Confi guration Settings Step 3CS, VOLUME (M3) must be selected.
2. In Confi guration Settings Step 4CS, “On 0” must be selected.
3. In Confi guration Settings Step 5CS, Alt B must be selected. The “B” control will be connected
to the “B” port of the MAV Motorized Alternating Valve and will have no electrical connection
to the MAV.
4. In Volume Installer Display Settings Step 2I, enter the volumetric capacity for the system.
(This must be the same as Valve A.)
5. In Volume Installer Display Settings Step 3I, set Days Override to OFF.